The BW 156 braking is designed for drives with frequency converters of small to medium output. Installation in and outside the control cabinet is possible.
In addition to the high protection class IP66, the profile resistors REOHM 156 are also UL-certified and have a power of 50 W up to 7.500 W (as combination).
Optional
Type |
Resistance values R [Ohm] |
Continous power at 25° C P [W] |
Max. operating voltage U [V DC] / [V AC] |
BW 156/400 |
0,3 - 2000 |
400 |
900 / 600 |
BW 156/600 |
0,3 - 2000 |
600 |
900 / 600 |
BW 156/800 |
1 - 2000 |
800 |
900 / 600 |
BW 156/1000 |
1 - 2000 |
1000 |
900 / 600 |
BW 156/1200 |
1 - 2000 |
1200 |
900 / 600 |
BW 156/1500 |
1 - 2000 |
1500 |
900 / 600 |
BW 156/2000 |
0,5 - 1000 |
2000 |
900 / 600 |
BW 156/2400 |
0,5 -1000 |
2400 |
900 / 600 |
BW 156/3000 |
0,5 - 1000 |
3000 |
900 / 600 |
BW 156/4500 |
0,3 -1000 |
4500 |
900 / 600 |
BW 156/6000 |
0,3 - 1000 |
6000 |
900 / 600 |
BW 156/7500 |
0,3 - 1000 |
7500 |
900 / 600 |
Higher power ratings on request
The ratings apply for 100 % duty cycle and free access and exit of cooling air.
In general: Is the ambient temperature higher than 40 °C, the continuous power must be reduced by 5 % per 10 K temperature rise.
Type |
L1 [mm] |
L2 [mm] |
L3 [mm] |
L4 [mm] |
B1 [mm] |
B2 [mm] |
H [mm] |
D [mm] |
Connection cable |
BW 156/400 |
170 |
155 |
140 |
500 |
103 |
70 |
53 |
4,5 |
IP20/40 PTFE AWG14
|
BW 156/600 |
230 |
215 |
200 |
500 |
103 |
70 |
53 |
4,5 |
|
BW 156/800 |
300 |
285 |
270 |
500 |
103 |
70 |
53 |
4,5 |
|
BW 156/1000 |
370 |
355 |
340 |
500 |
103 |
70 |
53 |
4,5 |
|
BW 156/1200 |
450 |
435 |
420 |
500 |
103 |
70 |
53 |
4,5 |
|
BW 156/1500 |
600 |
585 |
570 |
500 |
103 |
70 |
53 |
4,5 |
Type |
L1 [mm] |
L2 [mm] |
L3 [mm] |
L4 [mm] |
B1 [mm] |
B2 [mm] |
H [mm] |
D [mm] |
Connection line |
BW 156/400 |
174 |
159 |
140 |
500 |
103 |
70 |
53 |
4,5 |
IP54/65 shielded 3x1,5 mm² |
BW 156/600 |
234 |
219 |
200 |
500 |
103 |
70 |
53 |
4,5 |
|
BW 156/800 |
304 |
289 |
270 |
500 |
103 |
70 |
53 |
4,5 |
|
BW 156/1000 |
374 |
359 |
340 |
500 |
103 |
70 |
53 |
4,5 |
|
BW 156/1200 |
454 |
439 |
420 |
500 |
103 |
70 |
53 |
4,5 |
|
BW 156/1500 |
604 |
589 |
570 |
500 |
103 |
70 |
53 |
4,5 |
Other fixing dimensions possible
IP20 / IP40 IP20 / IP40 with temperature switch
IP54 / IP65 IP54 / IP65 or higher with temperature switch
Depending on the design and execution various types of protection ratings can be realized up to IP66. At protection ratings less than / equal IP40 the temperature increase must be at the surface resistance max. 300K. For a higher degree of protection (> IP40) a maximum temperature increase of 200K is allowed.
Attention! Duration overtemperature values of> 200 K could result to an impairment of protection rating.
It is possible to control the temperature of the resistance by using a temperature switch. In case of exceeding a rated temperature the temperature switch opens and can, for example, trigger an existing signaling contact. The temperature switch is mounted externally in protection class IP20 / IP40 and provided with two connection strands.
At IP54 / IP65 or higher, the temperature switch is integrated in the resistance and provided the connection with a temperature resistant cable.
B1 B2
B3 B4
Type |
L1 [mm] |
L2 [mm] |
B1 [mm] |
B2 [mm] |
H1 [mm] |
H2 [mm] |
D [mm] |
design [mm] |
Connection cable |
BW 156/2000 |
600 |
360 |
300 |
270 |
73 |
53 |
8,5 |
BF 1 |
IP20/40 PTFE AWG14 |
BW 156/2400 |
680 |
440 |
300 |
270 |
73 |
53 |
8,5 |
BF 1 |
|
BW 156/3000 |
830 |
590 |
300 |
270 |
73 |
53 |
8,5 |
BF 1 |
|
BW 156/4500 |
830 |
590 |
430 |
400 |
73 |
53 |
8,5 |
BF 2 |
|
BW 156/6000 |
830 |
590 |
560 |
530 |
73 |
53 |
8,5 |
BF 3 |
|
BW 156/7500 |
830 |
590 |
690 |
660 |
73 |
53 |
8,5 |
BF 4 |
Type |
L1 [mm] |
L2 [mm] |
B1 [mm] |
B2 [mm] |
H1 [mm] |
H2 [mm] |
D [mm] |
design [mm] |
Connection cable |
BW 156/2000 |
600 |
364 |
300 |
270 |
73 |
53 |
8,5 |
BF 1 |
IP54 shielded 3x1,5 mm² |
BW 156/2400 |
680 |
444 |
300 |
270 |
73 |
53 |
8,5 |
BF 1 |
|
BW 156/3000 |
830 |
594 |
300 |
270 |
73 |
53 |
8,5 |
BF 1 |
|
BW 156/4500 |
830 |
594 |
430 |
400 |
73 |
53 |
8,5 |
BF 2 |
|
BW 156/ 6000 |
830 |
594 |
560 |
530 |
73 |
53 |
8,5 |
BF 3 |
|
BW 156/7500 |
830 |
594 |
690 |
660 |
73 |
53 |
8,5 |
BF 4 |
Other fixing dimensions possible.
Surface temperature BW 156 / 400
|
![]() |
Surface temperature BW 156 / 600
|
![]() |
![]() |
|
Surface temperature BW 156 / 800
|
Surface temperature BW 156 / 100
|
|
![]() |
![]() |
|
Surface temperature BW 156 / 1200
|
Surface temperature BW 156 / 1500
|
|
![]() |
![]() |
Surface temperature increase, even over temperature, describes the increase in surface temperature when loaded.
These performances are valid for continuous operation. The power values may be increased in the short-term operation as a function of the duty cycle multiplied by the appropriate factor in the following diagram, or by the following formula.